ADSS Double Layer All-Dielectric Cable For 100-400M Span
Characteristics of ADSS:
Light weight, small cable diameter, reducing the ice;
Can be continuously electric erection;
Using AT sheath, large span
Description:
ADSS Double Layer Cable is used for communication cable of overhead high-voltage electricity transmission system,also can be used at the areas where lighting is frequent or distance is big. Aramid yarn is used as the strength member to assure the tensile and strain Performance.Mainly installed at existing 220kV or lower voltage power lines . Two Jacket and stranded loose tube design
According to different Related Strength Tension which suitable different situation. Please check the Cable Performance Parameter according to the 10-30 KN.
Cable Performance Parameter | |||
Span meter | 200 | 300 | 400 |
Related Strength Tension(RTS) | 17.5 kn | 20.6 kn | 28 kn |
Max Allowable Tension(MAT) | 6.9 kn | 8.2 kn | 11.5 kn |
Average Annual Operation Tension(EDS) | 4.36 kn | 5.17 kn | 7.0 kn |
Young Modulus | 14.1 kn/mm2 | 15.2 kn/mm2 | 19.3 kn/mm2 |
Coefficient of Thermal Expansion | 4.4 10-6/℃ | 3.1 10-6/℃ | 2.4 0-6/℃ |
Allowable Crush Resistance | Long Term: 1100 n/100mm | Long Term: 1100 n/100mm | Long Term: 1100 n/100mm |
| Short Term: 2200 n/100mm | Short Term: 2200 n/100mm | Short Term: 2200 n/100mm |
Minimum Bending Radius | Operating: 220 mm | Operating: 220 mm | Operating: 220 mm |
| Installlation: 360 mm | Installlation: 360 mm | Installlation: 360 mm |
Temperature Range | Operating: -40∽ +70℃ | Operating: -40∽ +70℃ | Operating: -40∽ +70℃ |
| Installlation: -15∽ +60℃ | Installlation: -15∽ +60℃ | Installlation: -15∽ +60℃ |
Out Sheath Material | Electrical Resistance AT (Borealis material 6081) Sheath | ||
Electrical Resistance Corrosion Measures | Good performance of Electrical Resistance and Corrosion Resistance | ||
Note: | ice accretion 5MM,weed speed:30M/S |